EEEN71372: Power System Plant, Asset Management and Condition Monitoring

Coursework 2 – OHL Design Exercise

Coursework – Overhead Line Design Exercise

1.   Structure and format/presentation of the report and marking scheme

The report should not be more than 10 pages long from Section 1 to Section 5 (see below) and discussion should be included to justify the selection of any required design coefficients and insulator properties. Overall, the discussion of the findings and conclusion are important.

The report should be divided into 5 sections following the order below:

Section 1:    “Power rating calculations” (max one page)

Section 2:    “Complete tower diagrams” for the towers designed based on the two insulator types indicating

only the tower dimensions. (max one page)

Section 3:    “Internal clearances calculations”; Justify any assumed values (when required) and use figures

(when required) to support your calculations

Section 4:    “External clearances calculations”; Justify any assumed values (when required) and use figures

(when required) to support your calculations

Section 5:    “Discussion and Conclusions”. (max one page)

Note 1:    Figures/diagrams are marked and therefore when copied from course material will be marked to a minimum.

Note 2:   In case that the format of the report does not adhere to the requirements stated above then appearance will be marked to a minimum.

Note 3: Do not repeat information that is given by this coursework to your report (this will result in confusion and reduced marks).

How marks of the report are allocated (approximately):

Structure and overall presentation 20%

Clarity and professional quality of figures 20%   Required calculations with complete steps 20%

Discussion/Justification of any values implemented 20%

Overall discussions and outcomes from the different designs 20%

2.   Overhead Line Design

A new double circuit 66kV single Horse conductor transmission system is required to transfer energy from Manchester to Liverpool with a span length of 180m. The conductor is installed at 5ºC and 22% of its rated strength and has a maximum operating temperature of 110ºC. A U160BS insulator dish designation is used. Additional information about the conductor and the insulator used for the overhead line system are provided below.

Calculate the overhead line rating (in MVA) and the suspension tower basic dimensions required for proper operation of the overhead line system.

What will be the OHL design if the most optimum Rod composite insulator (Table 1below) is utilised? Indicate which other polymeric insulators could be used on this OHL design and explain why.

Your report should include the diagram(s) of the suspension tower indicating all the dimensions/distances required for the engineers to build the OHL. Justify any engineering decisions made in the calculation section. Any key discussion points that come from the different designs should be included in the conclusion section.

Conductor Details

Table 1 - Bare conductor details

Conductor Type

Code Name

Cond. Diameter

(mm)

Weight (kg/km)

Rated Strength

(kN)

Coefficient of linear

expansion

(ºC-1)

RAC at 20ºC (Ω/km)

RAC at 75ºC (Ω/km)

AAAC

Oak

14.0

324.5

35.07

23.0 E-06

0.2768

0.3316

AAAC

Poplar

20.1

659.4

70.61

23.0 E-06

0. 1390

0.1665

AAAC

Upas

24.7

997.5

106.82

23.0 E-06

0.0921

0.1104

AAAC

Rubus

31.5

1622

173.53

23.0 E-06

0.0574

0.0688

ACSR

Gopher

7.08

26.2

9.58

19.1 E-06

1.3000

1.6945

ACSR

Horse

14.0

73.4

61.26

15.3 E-06

0. 3230

0.5425

ACSR

Lynx

19.5

834

79.97

17.8 E-06

0.1532

0.1873

ACSR

Moose

31.8

1997.3

159.92

19.3 E-06

0.0560

0.0684

Insulator String Details

●    Required creepage distance: 5.6m

●    Total length of fittings: 0.45m

●    Insulator dish designation properties are provided in the table below:

Table 2 - Pin and Cap, and long-rod insulator details

Designation

Electro-mechanical failing load kN

Diameter D mm

Spacing P mm

creepage   distance mm

P

 

 

U 160 BS

160

280

146

315

U 160 BSP

160

330

146

440

U 160 BL

160

280

170

340

               D             

U 160 BLP

160

330

170

525

 

Electro-mechanical failing load kN

Section length  L mm

Dry Arc length P mm

creepage   distance mm

 

S248130V3

210

3302

2967

9060

S248130V5

210

3302

2967

11293

S248142V6

210

3607

3272

8491

S248142V7

210

3607

3272

12969

Cross-arm design

●    Top cross-arm design angle 11o

●    Mid cross-arm design angle 12o

●    Lower cross-arm design angle 13o

●    All cross-arms have the same length

Other Information

●    Ground clearance according to the standards

●    Shielding angle: 25o at no wind

●    Wind speed at which clearances must be maintained: 14.6 m/s

●    Maximum reduction in distance between   phase conductors (due to vertical movement resulted by the conductor galloping): 0.8 m

●    Minimum heat loss due to convection: 36.30 W/m

●     Minimum radiated heat loss: 15.40 W/m

●     Maximum solar heat gain: 11.30 W/m

Important assumptions

●    It is assumed that the tower body is rectangular and it has a width of 2.5m with the shield wire placed at the centre of the very top of the tower body.

●    The wind forces employed on the insulator and its weight can be neglected (since they are very small compared to the conductor forces).

●    The vertical movement of the conductor caused by galloping is considered only for the phase- to-phase clearances since the probability of having galloping under the maximum thermal rating of the line is negligible.